Electrical Panel Standard
IP of panels should be not less than IP‐65 if not higher degree is required.
Electrical Panel Standard
Under and over voltage protection and reverse phases by using protection relay.
Electrical Panel Standard
Install local disconnect switch with Lockout on the power cable feed the Motor.
Electrical Panel Standard
For the conveyors systems according to our understanding of the industry and for better and detailed control of the conveying system the motors will be equipped with a frequency drive, to control motor speed, start & stop smoothly and protect the motor.
Electrical Panel Standard
Install Emergency Switch on two positions “the start and the end of the line”.
Electrical Panel Standard
All wires are to be numbered with non-erasable labels.
Electrical Panel Standard
The power cable enters at the underside of the panel through cable gland.

Electrical Panel Standard

Our electrical panel design and implementation adhere to several standard requirements that must be taken into consideration and accommodated for:

Power and protection section (conveying system control and power panel)

1. IP of panels should be not less than IP‐65 if not higher degree is required.
2.Panels to be designed with at least 25% additional space for any future expansion.
3.Under and over voltage protection and reverse phases by using protection relay.
4.Install local disconnect switch with Lockout on the power cable feed the Motor.
5.Spaces between components should be considered in accordance with the catalog of each component.
6.For the conveyors systems according to our understanding of the industry and for better and detailed control of the conveying system the motors will be equipped with a frequency drive, to control motor speed, start & stop smoothly and protect the motor.
7.Frequency drive protection should be considered in accordance with its catalog manufacturer recommendations.
8.Install Emergency Switch on two positions “the start and the end of the line”.
9.Emergency button is to be installed on the door with clear label – and to be easily reachable by operator.
10.All wires are to be numbered with non-erasable labels.
11.The power cable enters at the underside of the panel through cable gland.